A new split-system central AC installed in Texas must be at least 14.3 SEER2 if it is under 45,000 Btu/h (about 3.75 tons) and 13.8 SEER2 if larger. A new split heat pump must be 14.3 SEER2 and 7.5 HSPF2. Texas is in DOE’s Southeast region, where the AC rule applies by installation date, so older stock that misses it cannot be installed here at all.

Independent publisher, not a contractor

Reviewed · 12 named sources · No named reviewer yet; see our editorial policy.

On this page (10)
  1. The numbers that apply in Dallas
  2. Why the installation date matters here
  3. SEER vs SEER2: why the old numbers do not translate
  4. Legal floor, ENERGY STAR and program thresholds
  5. How to check a quote in five minutes
  6. SEER2 and the refrigerant change are separate questions
  7. Choosing a level above the floor
  8. Common mistakes
  9. Sources
  10. Questions

The numbers that apply in Dallas

14.3 SEER2split AC under 45,000 Btu/h, installed in Texas
13.8 SEER2split AC 45,000 Btu/h and larger
14.3 · 7.5split heat pump SEER2 and HSPF2, nationwide

DOE puts Texas in the hot-humid Southeast region. Split-system central ACs installed there on or after 1 January 2023 must be at least 14.3 SEER2 below 45,000 Btu/h and 13.8 SEER2 at or above it. The Southeast has no EER2 minimum; that applies only in the Southwest.

Split heat pumps need 14.3 SEER2 and 7.5 HSPF2 nationwide.

Federal efficiency minimums that apply to a Texas installation
EquipmentMinimum (installed on or after 1 Jan 2023)Applies by
Split central AC, under 45,000 Btu/h14.3 SEER2Installation date (Southeast)
Split central AC, 45,000 Btu/h and up13.8 SEER2Installation date (Southeast)
Split heat pump14.3 SEER2 and 7.5 HSPF2Manufacture date (national standard)
EER2 for a split ACNo minimum in the SoutheastSouthwest only

45,000 Btu/h is 3.75 tons. A typical 2- to 3.5-ton Dallas replacement falls under the 14.3 line; a 4- or 5-ton system falls under the 13.8 line.

Why the installation date matters here

In the Southeast the split-AC standard is enforced by installation date, not manufacture date, and DOE defines installation as connecting the refrigerant lines or electrical systems to make the system operational. It calls installing a non-compliant split AC there illegal.

In the northern states, a unit built before 2023 to the old standard could still be installed until stock ran out. In Texas it could not: from 1 January 2023 the question is whether the system meets the regional standard on the day it is connected. That is why a Dallas homeowner never needs to accept “it was in the warehouse” as a reason for a low rating.

The coil counts too

An outdoor unit can be installed in the Southeast only if at least one coil-only combination of that model meets the regional standard; a blower-coil rating alone does not qualify it. In practice: ask for the AHRI certificate for the exact outdoor unit and indoor coil (or furnace and coil) being installed, not a brochure rating for the outdoor unit alone.

SEER vs SEER2: why the old numbers do not translate

DOE says SEER2, EER2 and HSPF2 are similar to the old SEER, EER and HSPF but not directly comparable, because the 2023 test procedure changed.

The new test runs the equipment against higher external static pressure, closer to what real duct systems impose, so the same machine usually posts a lower SEER2 number than its old SEER number. A quote that mixes the two metrics, or a sales sheet that quotes only “SEER”, is not wrong by itself, but it does not tell you whether the system clears the 2023 floor.

  • SEER2: seasonal cooling efficiency, the headline number for the regional minimum.
  • EER2: efficiency at a hot 95 °F test point. No Southeast minimum, but rebate programs and ENERGY STAR use it.
  • HSPF2: seasonal heating efficiency for a heat pump. 7.5 is the national floor for a split heat pump.

Legal floor, ENERGY STAR and program thresholds

The minimum is only the first rung. Utility programs and ENERGY STAR set their own, higher thresholds, and a rebate depends on clearing the program’s number, not the federal one.

Efficiency thresholds a Dallas homeowner may meet
SEER2What it isWhat it means for you
13.4North-region split AC minimumNot legal to install as a new split AC in Texas
13.8Southeast minimum, split AC 45,000 Btu/h and upLegal floor for roughly 3.75 tons and larger
14.3Southeast minimum, split AC under 45,000 Btu/h; national split heat pump minimumLegal floor for most Dallas homes
15.2ENERGY STAR level for split AC and heat pumpsCertification threshold, not a legal requirement
15.3Garland program threshold (program listed as ending 30 Sep 2026)Example of a utility threshold above the floor

ENERGY STAR’s central AC level for split systems is 15.2 SEER2 and 12.0 EER2. ENERGY STAR certifies split air-source heat pumps at 7.8 HSPF2, 15.2 SEER2 and 11.0 EER2 or better.

The City of Garland’s central air conditioning and heat pump program required a total system change-out at 15.3 SEER2 or better and was listed as ending 30 September 2026 or when funds ran out. The page gives no rebate amount. Oncor’s 2026 program sets its own floor for split systems (11.6 EER) and pays through participating contractors; see Dallas AC rebates by utility.

A threshold is not a promise of savings

This page deliberately gives no “savings per SEER2 point” figure. Savings depend on your rate plan, your ducts and how the system was sized, and no source we trust publishes a Dallas number. If a quote promises a dollar saving, ask how it was calculated.

How to check a quote in five minutes

  1. Find the model numbers for the outdoor unit and the indoor coil or air handler (and the furnace, if the coil sits on one).
  2. Ask for the AHRI certificate of that exact combination. The AHRI number is on it, with the certified SEER2, EER2 and, for heat pumps, HSPF2.
  3. Check the capacity on the certificate: under or over 45,000 Btu/h decides whether 14.3 or 13.8 applies.
  4. Compare against the program you want (ENERGY STAR, Oncor through the contractor, a city utility). Ask the contractor in writing whether the combination qualifies.
  5. Keep the certificate with the invoice. Oncor’s program requires it for HVAC projects, and it is the proof if the rating is ever questioned. HVAC projects are documented with an AHRI certificate, a Manual J load calculation where the unit requires it, before-and-after nameplate photos, and a signed customer agreement.

SEER2 and the refrigerant change are separate questions

Equipment made or imported since 1 January 2025 uses lower-GWP A2L refrigerants (R-454B or R-32) instead of R-410A. An EPA rule finalized in May 2026, effective 27 July 2026, removed the 1 January 2026 cutoff, so contractors may install pre-2025 R-410A systems until that stock runs out.

A system can meet SEER2 on either refrigerant. Whether you are quoted R-410A stock or an R-454B or R-32 system is a cost and service question, covered in R-410A vs the new refrigerants. Do not let one stand in for the other on a quote.

Choosing a level above the floor

With about 20 days a year at 100 °F or hotter, cooling efficiency matters more in Dallas than in most of the country. That argues for looking above the floor, but it does not make the most efficient system the right one. Two-stage and variable-speed equipment costs more, and on the published DFW ranges, stepping up to 16+ SEER2 adds roughly $1,000–$3,000.

  1. Get the floor price and one step-up price from the same contractor, on the same scope.
  2. Ask whether the step-up qualifies for a program you can actually use (your utility, ENERGY STAR).
  3. Ask what the step-up changes besides the rating: stages, humidity control, sound.
  4. Check the ducts first. ENERGY STAR estimates that about 20 to 30 percent of the air moving through a typical duct system is lost to leaks, holes and poorly connected ducts.
  5. Compare the quotes line by line in the quote comparison tool.

Common mistakes

  • Reading the outdoor unit’s brochure rating. The certified rating belongs to the matched combination.
  • Replacing only the outdoor unit on an old coil. The pair may not be a certified combination at all; see the coil-only guide.
  • Counting a federal tax credit. The federal Energy Efficient Home Improvement Credit (25C) applied to qualifying property placed in service before 31 December 2025. It is not available for a system installed in 2026.
  • Assuming a rebate. Program thresholds are higher than the legal floor and funding runs out.
  • Comparing SEER to SEER2. They are measured differently.

For the bigger picture of what a matched system costs, see the Dallas AC installation cost guide; the national explainer on regional standards lives on our sister site, HyreHVAC.

Sources

Questions

What is the minimum SEER2 for a new AC in Texas?

14.3 SEER2 for a split-system central AC under 45,000 Btu/h, and 13.8 SEER2 at 45,000 Btu/h and above, for systems installed on or after 1 January 2023.

Can a contractor still install a 13 or 14 SEER unit in Dallas?

Only if the matched system is certified at or above the 2023 SEER2 minimum. Old SEER ratings do not translate directly, so ask for the AHRI certificate.

Is there an EER2 requirement in Texas?

Not for the federal minimum. The EER2 minimum applies in the Southwest region. Utility programs and ENERGY STAR may require one.

What HSPF2 does a heat pump need?

7.5 HSPF2 for a split heat pump nationwide; ENERGY STAR uses 7.8.

Do I need a high SEER2 unit to get the Oncor incentive?

The 2026 Oncor manual requires split systems to reach 11.6 EER and documents each job with an AHRI certificate. The participating contractor determines eligibility and files the paperwork.

Next step

Free quote request

Get a quote to check against these numbers

  1. Tell us about the job. Service, ZIP, property and timing. The form says right away if your ZIP is outside the area.
  2. We check the license first. Requests go only to contractors whose TDLR air conditioning license we have matched on the state register. None is signed yet: if no checked contractor covers your ZIP, we email you and say so.
  3. Compare what comes back. Line the written quotes up in the quote-comparison tool.

No cost and no obligation. We are a publisher, not a contractor. Partner contractors will pay us for introductions; none is signed yet. How that works.

Request AC installation quotes

Free and no obligation. We pass a request on only to a contractor whose TDLR license we have checked and who covers your ZIP.

Enter a Dallas–Fort Worth ZIP (750–753, 760–762). Outside that, we do not have a partner yet.
Please add your name.
A phone number is how the contractor reaches you.
Please add a working email.
Get installation quotes